Kentec Syncro AS
Double address (fault announced at loop initialisation)
Per the manual, the control panel can detect devices that have been set to the same address and will announce a “Double address” fault if it finds any. It cannot tell which devices are double addressed. To help find…
View on the Kentec Syncro AS pageNotifier by Honeywell ID3000
System Fault 43 - FLASH Memory Checksum
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 45 - FLASH Memory Write Error
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageFike Twinflex
POWER FAULT LED (flashing)
Yellow POWER FAULT indicator, flashing: the manual says a mains supply fault has been detected, and to check for a 230 V AC supply on the incoming AC terminals.
View on the Fike Twinflex pageFike Twinflex
SYSTEM FAULT LED (flashing, write enable)
Yellow SYSTEM FAULT indicator, flashing: the manual says this LED is also illuminated if the write protect / write enable switch is left on while the system is not in the engineer menu. In access levels 1 and 2 a system…
View on the Fike Twinflex pageC-TEC ZFP
Fault LED (flashing yellow)
Per the manual's LED table, a flashing yellow Fault indicator means there is a fault condition on the system. See section 5.3 for details.
View on the C-TEC ZFP pageC-TEC ZFP
Sounder Fault LED (flashing yellow)
Per the manual, a flashing yellow Sounder Fault indicator means a fault has been detected on the panel's sounder circuits; steady yellow means the panel's sounders have been disabled. Action listed: call the service…
View on the C-TEC ZFP pageFike Safety Technology Quadnet
POWER FAULT LED (flashing: mains)
Yellow POWER FAULT indicator, flashing: the manual says the mains supply has failed, and to check the fuse and the 230 V AC supply on the PCB AC terminals.
View on the Fike Safety Technology Quadnet pageNotifier by Honeywell ID3000
Fault 48 - Base PCB/Expansion h/w fault
No separate cause description is given for this message beyond its name. Action: Change the Base PCB (PN: 020-568) or Extension Chassis with Display Module Kit (PN: 020-559-XXX).
View on the Notifier by Honeywell ID3000 pageProtec 6500
Network Fault - Network Master Elected
The network has unexpectedly lost the master panel, so another panel has automatically been assigned as master until the problem is fixed.
View on the Protec 6500 pageProtec 6500
Network Card Flash Checksum Fault
There is a memory corruption in the network card; replace the card.
View on the Protec 6500 pageZiton ZP2-FR
Fire protection fault
The yellow Fire Protection Fault/Disabled/Test LED indicates a fire protection fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Sounder fault
The yellow Sounder Fault/Disabled/Test LED indicates a sounder fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series Installation Manual,…
View on the Ziton ZP2-FR pageKentec Syncro AS
SOUNDER FAULT
The sounder fault/disabled indicator lights when any output treated as a sounder is faulty or disabled. Syncro AS treats an output as a sounder when its Silenceable and Evacuate Output attributes are selected. The same…
View on the Kentec Syncro AS pageHaes Systems Esento Excel 2-12 Zone
Repeater fault: faulty repeater
When a repeater fault is displayed, press and hold ENTER: a slow flash of the Repeater Fault LED indicates a faulty repeater. Red fire LEDs 1 to 8 show which repeater was offline, and amber fault LEDs 1 to 8 show which…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Repeater fault: network cable error
When a repeater fault is displayed, press and hold ENTER: a fast flash of the Repeater Fault LED indicates a network cable error.
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Repeater fault: repeater off line
When a repeater fault is displayed, press and hold ENTER: a normal flash of the Repeater Fault LED indicates the repeater is off line. Red fire LEDs 1 to 8 show which repeater was off line.
View on the Haes Systems Esento Excel 2-12 Zone pageEMS Fire FireCell
Unassigned
In the device Fault Status menu, this indicates the device is not yet assigned to the system. Assign it via the rotary control or the Assign Devices menu option.
View on the EMS Fire FireCell pageC-TEC CFP (2/4/8 Zone Standard Conventional)
System Fault: PLL
Occurs as a result of a momentary disturbance in the panel's microprocessor. In access level three fault diagnosis this shows as Zone 3's Fault light lit.
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP AlarmSense (2/4/8 Zone)
System Fault: PLL
Occurs as a result of a momentary disturbance in the panel's microprocessor. In access level three fault diagnosis this shows as Zone 3's Fault light lit.
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageKentec Syncro AS
Earth fault
The panel has detected leakage to earth; the manual specifies indication below 30 kOhm from +28 V or 0 V to earth.
View on the Kentec Syncro AS pageMorley-IAS ZXSe
Earth Fault
Yellow Earth Fault indicator on the ZX series panel: an earth connection fault has occurred on a cable. To clear it, correct the fault condition and then perform a panel reset (page 7). The alphanumeric display shows a…
View on the Morley-IAS ZXSe pageMorley-IAS ZXSe
Fault
Front-panel indicator on the ZX series panel. Function per the manual: the panel has detected a fault (yellow indicator). How to clear, per the manual: correct the condition causing the fault and then perform a panel…
View on the Morley-IAS ZXSe pageMorley-IAS ZXSe
System / CPU Fault
Front-panel indicator on the ZX series panel. Function per the manual: the CPU has reset or a system fault has occurred (yellow indicator). How to clear, per the manual: correct the problem, if appropriate, and then…
View on the Morley-IAS ZXSe pageMorley-IAS ZXSe
Zone Fault
Front-panel indicator on the ZX series panel. Function per the manual: flashing means the zone contains faulty devices; steady means the zone is either disabled or in test mode (yellow zone indicator). How to clear, per…
View on the Morley-IAS ZXSe pageFireClass FC501
PRINTER x FAULT
The source names this fault message and gives only the applicable module/input numbering (x from 1 to 4); it states no cause, meaning, or remedy beyond that numbering. No cause is asserted here beyond what the source…
View on the FireClass FC501 pageMorley-IAS DX (Dimension Series DX1e/DX2e/DX4e)
Earth Fault
Front-panel indicator on the DX Dimension Series panel (yellow). Function per the manual: an earth connection fault has occurred on a cable. How to clear, per the manual: correct the fault condition and then perform a…
View on the Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e) pageMorley-IAS DX (Dimension Series DX1e/DX2e/DX4e)
FAULT
Front-panel indicator on the DX Dimension Series panel (yellow). Function per the manual: the panel has detected a fault. How to clear, per the manual: correct the condition causing the fault and then perform a panel…
View on the Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e) pageMorley-IAS DX (Dimension Series DX1e/DX2e/DX4e)
System / CPU Fault
Front-panel indicator on the DX Dimension Series panel (yellow). Function per the manual: the CPU has reset or a system fault has occurred. How to clear, per the manual: correct the problem, if appropriate, and then…
View on the Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e) pageHochiki HFP AP-1AS/2AS
Fault events are non-latching (Reset does not clear them)
Per the user manual, the Reset button is used to reset any activation defined as a latching input type, which includes fire and pre-alarm events. In general, fault events are non-latching and cannot be cleared by…
View on the Hochiki HFP AP-1AS/2AS page