Panel fault records

Fault records by panel

Fault records for a small, deliberately staged set of panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from. More panels are added as more records go through source review.

Searches 148 records across 6 panels.

22 partial matches for “Syncro XT”

Nothing matched every word, so these match some of them. Check the record and panel before relying on it.

Kentec Syncro AS

ZONE FAULT

Legacy record reviewed

A conventional zone circuit has reported an open or short circuit fault. Kentec Syncro AS monitors zone wiring with end-of-line resistors (EOLR).

View on the Kentec Syncro AS page

Notifier by Honeywell ID3000

Earth Fault

Not yet verified

The earth fault monitor detects the presence of an earth on the positive or negative sides of the system. Should this condition occur, disconnect the field circuit wiring one cable at a time and view the LED at the top…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 48 - Base PCB/Expansion h/w fault

Not yet verified

No separate cause description is given for this message beyond its name. Action: Change the Base PCB (PN: 020-568) or Extension Chassis with Display Module Kit (PN: 020-559-XXX).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 71 - Config. needs Expansion Card

Not yet verified

This fault message can only appear when ID3000 panels are networked with earlier compatible panels; it is not applicable to the 'local' ID3000 Series panel. Where it is applicable, an Extension Chassis with Display…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Short Circuit

Not yet verified

A short circuit has occurred on the loop between the panel and isolator (if fitted). If isolators are fitted, the system shows NO REPLY/MISSING for the devices located between the isolation points, or LOSS OF PART LOOP…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Terminal Link Fault

Not yet verified

This fault indicates that the peripheral unit connected to the third-party-protocol RS232 port has not responded to the enquiry code sent, or the link to the third-party equipment is not connected (this would normally…

View on the Notifier by Honeywell ID3000 page

Advanced MxPro 4

DEVICE MISSING

Not yet verified

Shown against the specific loop address, zone and location text on the display, e.g. "1 004.0 DEVICE MISSING" under the zone's fault list. Indicates the panel is no longer receiving a response from that addressed device.

View on the Advanced MxPro 4 page

Advanced MxPro 5

Device Missing

Not yet verified

The panel display shows the affected zone and device text with "DEVICE MISSING" alongside the device type (e.g. "(MULTI.SENSOR)"), from a worked example in the official Advanced MxPro5 User Manual (section 3.3, Fault…

View on the Advanced MxPro 5 page

Advanced MxPro 5

SERVICE DUE

Not yet verified

The panel raises this fault once the programmed "next service due" date is reached, alerting the site operator that a maintenance visit is overdue. It clears automatically once a new service date is entered. From the…

View on the Advanced MxPro 5 page

Ziton ZP2-FR

Battery charger: compensation

Not yet verified

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: overvoltage

Not yet verified

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: sensor HI

Not yet verified

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: sensor LO

Not yet verified

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: undervoltage

Not yet verified

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Kentec Syncro AS

Aux. 24V fuse failed

verified

The panel has detected operation of the monitored self-resetting 500 mA auxiliary 24 V output protection.

View on the Kentec Syncro AS page

Kentec Syncro AS

BAD DATA

verified

The panel has received invalid loop data from one device on four consecutive polls.

View on the Kentec Syncro AS page

Kentec Syncro AS

BATTERY DISCONNECTED

verified

The panel power-supply monitoring cannot detect the connected standby battery set.

View on the Kentec Syncro AS page

Kentec Syncro AS

BATTERY LOW VOLTAGE

verified

The monitored standby battery voltage has fallen to the panel low-voltage threshold.

View on the Kentec Syncro AS page

Kentec Syncro AS

Earth fault

verified

The panel has detected leakage to earth; the manual specifies indication below 30 kOhm from +28 V or 0 V to earth.

View on the Kentec Syncro AS page

Kentec Syncro AS

MAINS FAILED

verified

The panel power-supply monitoring has detected loss of the mains supply.

View on the Kentec Syncro AS page

Kentec Syncro AS

SOUNDER FAULT

Legacy record reviewed

A monitored sounder or bell circuit has reported an open or short circuit. The circuit is monitored at rest to ensure sounders will function when called on.

View on the Kentec Syncro AS page

Kentec Syncro AS

unexpected network card

verified

The panel has detected a newly installed network card not yet stored in its configuration.

View on the Kentec Syncro AS page