Skip to main content
Panel fault records

Fault records by panel

Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.

Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.

Want to test yourself? Try the free daily fault challenge.

9 partial matches for “Twinflex fault finding”

Nothing matched every word, so these match some of them. Check the record and panel before relying on it.

Fike Twinflex

EARTH FAULT LED

Source-checked

Yellow EARTH FAULT indicator, flashing: the manual says an earth fault has been detected where a path exists from the circuit wiring to earth. Remove circuits one at a time to discover which one, and then rectify.

View on the Fike Twinflex page

Fike Twinflex

FAULT LED

Source-checked

Yellow FAULT indicator, continuous: the manual says the control panel is in the fault state and other indicators will show the origin. The indication can also be confirmed from the message in the panel information…

View on the Fike Twinflex page

Fike Twinflex

FIRE OUTPUT fault LED

Source-checked

Yellow FIRE OUTPUT indicator, flashing: the manual says a fault condition is present on a monitored relay circuit. Continuous means a device or an action associated with the monitored relay circuit has been disabled.

View on the Fike Twinflex page

Fike Twinflex

POWER FAULT LED (continuous)

Source-checked

Yellow POWER FAULT indicator, continuous: the manual says a battery fault has been detected, and to check the batteries and the in-line battery fuse.

View on the Fike Twinflex page

Fike Twinflex

POWER FAULT LED (flashing)

Source-checked

Yellow POWER FAULT indicator, flashing: the manual says a mains supply fault has been detected, and to check for a 230 V AC supply on the incoming AC terminals.

View on the Fike Twinflex page

Fike Twinflex

SOUNDER fault LED

Source-checked

Yellow SOUNDER indicator, flashing: the manual says a fault condition is present on a monitored sounder circuit. Continuous means a device or an action associated with the monitored sounder circuits has been disabled.

View on the Fike Twinflex page

Fike Twinflex

SYSTEM FAULT LED (continuous)

Source-checked

Yellow SYSTEM FAULT indicator, continuous: the manual says it indicates the presence of a processor or a checksum error. To clear it, power the system down, reprogram all settings and test the system. During a system…

View on the Fike Twinflex page

Fike Twinflex

SYSTEM FAULT LED (flashing, write enable)

Source-checked

Yellow SYSTEM FAULT indicator, flashing: the manual says this LED is also illuminated if the write protect / write enable switch is left on while the system is not in the engineer menu. In access levels 1 and 2 a system…

View on the Fike Twinflex page

Fike Twinflex

ZONE fault LED

Source-checked

Yellow ZONE indicator, flashing: the manual says a fault condition is present on one of the zones or on a device connected to that zone. Continuous means a device or an action associated with a zone has been disabled.

View on the Fike Twinflex page

Browse by manufacturer

49 panels

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.