C-TEC XFP

Investigating a device with INTENSIVE DEVICE MONITOR

Source-checked

Per the manual, this function monitors one addressable point under intensive, repeated polls from the panel, and reports how many good and bad polls occur between the panel and the device, which can help pinpoint loop…

View on the C-TEC XFP page

Ziton ZP2-FR

Battery charger: compensation

Source-checked

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: overvoltage

Source-checked

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: sensor HI

Source-checked

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: sensor LO

Source-checked

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: undervoltage

Source-checked

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Fire protection fault

Source-checked

The yellow Fire Protection Fault/Disabled/Test LED indicates a fire protection fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Firenet panel offline

Source-checked

If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Mains / mains fuse fault

Source-checked

The yellow Supply Fault LED indicates a power supply fault. A steady LED indicates a mains or mains fuse fault (a flashing LED indicates a battery fault). From the ZP2 Series Installation Manual, Table 3 "Common…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Sounder fault

Source-checked

The yellow Sounder Fault/Disabled/Test LED indicates a sounder fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series Installation Manual,…

View on the Ziton ZP2-FR page

Fike Twinflex

SYSTEM FAULT LED (flashing, write enable)

Source-checked

Yellow SYSTEM FAULT indicator, flashing: the manual says this LED is also illuminated if the write protect / write enable switch is left on while the system is not in the engineer menu. In access levels 1 and 2 a system…

View on the Fike Twinflex page

Zeta Simpo

EXT Output Open

Source-checked

Event message on the SIMPO addressable panel. The manual's Appendix A table describes it as: Circuit broken at Extinguishing output. The manual gives no cause or action for this message.

View on the Zeta Simpo page

Zeta Simpo

Fault Output Open

Source-checked

Event message on the SIMPO addressable panel. The manual's Appendix A table describes it as: Circuit broken at Fault output. The manual gives no cause or action for this message.

View on the Zeta Simpo page

Zeta Simpo

Fire Output Open

Source-checked

Event message on the SIMPO addressable panel. The manual's Appendix A table describes it as: Circuit broken at Fire output. The manual gives no cause or action for this message.

View on the Zeta Simpo page

Zeta Simpo

New Loop Devices Found

Source-checked

Event message on the SIMPO addressable panel. The manual's Appendix A table describes it as: New loop devices are found in system configuration. The manual gives no cause or action for this message.

View on the Zeta Simpo page

Zeta Simpo

New Periphery Devices Found

Source-checked

Event message on the SIMPO addressable panel. The manual's Appendix A table describes it as: New periphery devices are found in the system configuration. The manual gives no cause or action for this message.

View on the Zeta Simpo page

Nittan Evolution

DOUBLE ADDRESS FAULT

Source-checked

Two or more devices may have the same address setting. All devices with the same address will answer at the same time and the panel will not be able to understand the reply it receives. Search the detailed loop report…

View on the Nittan Evolution page

FireClass FC501

MFI x COMMUNIC.

Source-checked

The source names this fault message and gives only the applicable module/input numbering (x from 1 to 4); it states no cause, meaning, or remedy beyond that numbering. No cause is asserted here beyond what the source…

View on the FireClass FC501 page

FireClass FC501

MFI x INy SHORT

Source-checked

The source names this fault message and gives only the applicable module/input numbering (x from 1 to 4; y from 1 to 5); it states no cause, meaning, or remedy beyond that numbering. No cause is asserted here beyond…

View on the FireClass FC501 page

FireClass FC501

MFI x SERIAL CHANN.

Source-checked

The source names this fault message and gives only the applicable module/input numbering (x from 1 to 4); it states no cause, meaning, or remedy beyond that numbering. No cause is asserted here beyond what the source…

View on the FireClass FC501 page

FireClass FC501

PRINTER x ABSENT

Source-checked

The source names this fault message and gives only the applicable module/input numbering (x from 1 to 4); it states no cause, meaning, or remedy beyond that numbering. No cause is asserted here beyond what the source…

View on the FireClass FC501 page

FireClass FC501

PRINTER x FAULT

Source-checked

The source names this fault message and gives only the applicable module/input numbering (x from 1 to 4); it states no cause, meaning, or remedy beyond that numbering. No cause is asserted here beyond what the source…

View on the FireClass FC501 page

Siemens Fire Safety Cerberus PRO FC726

Topology is invalid

Source-checked

Displayed after a C-NET detector line has been read in, if the topology of that line is invalid (source gives four invalid-topology diagrams: stub on stub or loop interrupted; stub on stub on loop; several stubs…

View on the Siemens Fire Safety Cerberus PRO FC726 page

Protec 6100

General fault handling

Source-checked

The manual says that when the 6100 detects a fault in any of the critical operating paths it shows it on the front panel display and the internal buzzer pulses slowly. The General Fault indicator is illuminated and is…

View on the Protec 6100 page

Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e)

INPUT OPEN CIRCUIT

Source-checked

Panel fault text shown on the DX display. The manual's example shows it as an input open circuit on 'Monitored Input 1' registered at 12:15, as one of three panel-related faults. The manual gives it only as an example…

View on the Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e) page

Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e)

NO REPLY FROM DEVICE

Source-checked

Fault text shown on the DX display for a loop device. The manual's examples show it beside the zone, loop number, device address (for example L1 A010), device type and the time the device entered the fault condition.…

View on the Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e) page

Fike Safety Technology CIE-A-200

Device faults during initialisation

Source-checked

Per the manual, if the system detects a device fault or fire activation during initialisation, initialisation does not fail at that point. Beyond certain limits initialisation will fail and the various fault or fire…

View on the Fike Safety Technology CIE-A-200 page

Fike Safety Technology CIE-A-200

Earth Fault

Source-checked

Per the manual, if the panel detects a short circuit or leakage current to earth/screen from one of its supply rails (0 V or +Ve) an Earth Fault is displayed. The normal voltage between 0 V and Earth SCRN is 1.7 V; the…

View on the Fike Safety Technology CIE-A-200 page

Fike Safety Technology CIE-A-200

Loop not complete (loop +ve to -ve short circuit or +ve open circuit at initialisation)

Source-checked

Per the manual, if the system faces a loop +ve to -ve short circuit or a loop +ve open circuit during initialisation, initialisation fails at that point and a message of Loop not complete is displayed. Devices up to…

View on the Fike Safety Technology CIE-A-200 page

Fike Safety Technology Quadnet

Smoke Sensor Failed - Signal High

Source-checked

Per the manual: make sure the correct device is being investigated by comparing its description with the device address and/or serial number; make sure the optical chamber is clean, and if not replace it with a new one…

View on the Fike Safety Technology Quadnet page