C-TEC XFP
General Fault
Yellow General Fault indicator on the XFP: the manual says it flashes yellow when there is a fault condition on the panel, and will always be lit in conjunction with at least one other fault LED.
View on the C-TEC XFP pageC-TEC XFP
Power Supply Fault
Yellow Power Supply Fault indicator on the XFP: the manual says it is lit yellow when the panel's power supply or mains has failed, or the panel's standby battery is in poor condition.
View on the C-TEC XFP pageC-TEC XFP
System Fault
Amber System Fault indicator on the XFP: the manual says it is lit amber when a system error, such as a microprocessor fault, occurs, and it remains lit even if the panel automatically clears the fault.
View on the C-TEC XFP pageC-TEC XFP
Fault conditions (what the display shows, including Device Missing example)
Per the user manual, if part of the fire alarm system fails (for example detector failure or a wiring fault), one or more of the panel's fault indicators flash, the internal sounder (if enabled) pulses, and the display…
View on the C-TEC XFP pageC-TEC XFP
Earth fault
The XFP earth-fault monitoring has detected an abnormal connection between the fire system and earth.
View on the C-TEC XFP pageC-TEC XFP
PSU fault
The XFP power-supply monitoring indicates a supply, battery or earth-monitoring problem.
View on the C-TEC XFP pageC-TEC XFP
Sounder Status
Sounder Status indicator on the XFP: the manual says it flashes yellow when a fault is detected on either of the panel's two conventional sounder circuits, or if there is a sounder disablement anywhere on the system.
View on the C-TEC XFP pageC-TEC XFP
Investigating a device with INTENSIVE DEVICE MONITOR
Per the manual, this function monitors one addressable point under intensive, repeated polls from the panel, and reports how many good and bad polls occur between the panel and the device, which can help pinpoint loop…
View on the C-TEC XFP pageC-TEC XFP
Locating loop open or short circuits: BLINK DETECTOR LEDS
Per the manual, this engineering function momentarily asserts the LED outputs of loop devices in one continual sweep, and is useful for locating open or short circuit faults on the loop wiring. LEDs are asserted step by…
View on the C-TEC XFP page