Ziton ZP3
Internal supply LEDs 37, 15, 14, 8, 7, 2 and 4
The legend lists these green LEDs as supply indicators: on means the supply is on and off means the supply is faulty. LED 37: internal 24 V DC supply. LED 15: internal supply for the CPU (5 V DC). LED 14: internal…
View on the Ziton ZP3 pageZiton ZP3
Power supply LED 18: earth fault
Diagnostic LED 18 on the ZP3 power supply/main board: the legend lists it as default off, and green on means an earth fault.
View on the Ziton ZP3 pageZiton ZP3
Fuse ratings on the power supply board
The legend lists: F6 auxiliary 24 V DC supply, F4AL250V (20 x 5 mm, 4.0 A fast-blow); F1 battery fuse, S6300mAL250V (20 x 5 mm, 6.3 A slow-blow); F8 and F7 monitor sound, F1AL250V (1.0 A fast-blow); F5 RMC FLT alarm,…
View on the Ziton ZP3 pageZiton ZP3
LED 1: battery charging
LED 1 is listed in the legend as the battery charging indicator.
View on the Ziton ZP3 pageZiton ZP3
Power supply LED 19: loop fault
Diagnostic LED 19: the legend lists it as default off, and green on means a loop fault.
View on the Ziton ZP3 pageZiton ZP3
Power supply LED 20: sounder fault
Diagnostic LED 20: the legend lists it as default off, and green on means a sounder fault.
View on the Ziton ZP3 pageZiton ZP3
Power supply LED 21: ADC failure
Diagnostic LED 21: the legend lists it as default off, and green on means an ADC (analogue-to-digital converter) failure.
View on the Ziton ZP3 page