Fault records by panel
Fault records for a small, deliberately staged set of panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from. More panels are added as more records go through source review.
Searches 148 records across 6 panels.
15 matches for “Ziton”
Ziton ZP2-FR
Battery charger: compensation
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: overvoltage
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: sensor HI
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: sensor LO
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: undervoltage
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery disconnected
The batteries are disconnected or no batteries are installed. A flashing Supply Fault LED accompanies this LCD message.
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery fault
The batteries may be damaged. A flashing Supply Fault LED accompanies this LCD message.
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery high resistance FLT
The batteries may be damaged or fully discharged. A flashing Supply Fault LED accompanies this LCD message.
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery short circuit
There is a battery cable short circuit. A flashing Supply Fault LED accompanies this LCD message. For any of the four battery fault messages in this table, the source directs: check the battery cables; if the cables are…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Earth fault
The yellow Earth Fault LED indicates an earth isolation fault. Earth fault reporting can be switched off under Panel setup > Other settings > Fault notification ("Earth", available on fire alarm control panels and…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Fire protection fault
The yellow Fire Protection Fault/Disabled/Test LED indicates a fire protection fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Firenet panel offline
If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Mains / mains fuse fault
The yellow Supply Fault LED indicates a power supply fault. A steady LED indicates a mains or mains fuse fault (a flashing LED indicates a battery fault). From the ZP2 Series Installation Manual, Table 3 "Common…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Sounder fault
The yellow Sounder Fault/Disabled/Test LED indicates a sounder fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series Installation Manual,…
View on the Ziton ZP2-FR pageZiton ZP2-FR
System Overload
Added to the event log when one or more event types (alarm, zone alarm, fault, condition, etc.) exceed the maximum limit of 512 events per type — this limit applies at panel level and per system, including repeater…
View on the Ziton ZP2-FR pagePanels
Notifier by Honeywell
ID3000
49 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 4
15 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 5
19 sourced fault records
View fault recordsZiton
ZP2-FR
15 sourced fault records
View fault recordsKentec Electronics
Kentec Syncro AS
7 sourced fault records
View fault recordsProtec
Protec 6500
38 sourced fault records
View fault records