Ziton ZP2-FR
Battery charger: compensation
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: overvoltage
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: sensor HI
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: sensor LO
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: undervoltage
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery disconnected
The batteries are disconnected or no batteries are installed. A flashing Supply Fault LED accompanies this LCD message.
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery fault
The batteries may be damaged. A flashing Supply Fault LED accompanies this LCD message.
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery high resistance FLT
The batteries may be damaged or fully discharged. A flashing Supply Fault LED accompanies this LCD message.
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery short circuit
There is a battery cable short circuit. A flashing Supply Fault LED accompanies this LCD message. For any of the four battery fault messages in this table, the source directs: check the battery cables; if the cables are…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Earth fault
The yellow Earth Fault LED indicates an earth isolation fault. Earth fault reporting can be switched off under Panel setup > Other settings > Fault notification ("Earth", available on fire alarm control panels and…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Fire protection fault
The yellow Fire Protection Fault/Disabled/Test LED indicates a fire protection fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Firenet panel offline
If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Mains / mains fuse fault
The yellow Supply Fault LED indicates a power supply fault. A steady LED indicates a mains or mains fuse fault (a flashing LED indicates a battery fault). From the ZP2 Series Installation Manual, Table 3 "Common…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Sounder fault
The yellow Sounder Fault/Disabled/Test LED indicates a sounder fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series Installation Manual,…
View on the Ziton ZP2-FR pageZiton ZP2-FR
System Overload
Added to the event log when one or more event types (alarm, zone alarm, fault, condition, etc.) exceed the maximum limit of 512 events per type — this limit applies at panel level and per system, including repeater…
View on the Ziton ZP2-FR pageZiton ZP3
Fuse ratings on the power supply board
The legend lists: F6 auxiliary 24 V DC supply, F4AL250V (20 x 5 mm, 4.0 A fast-blow); F1 battery fuse, S6300mAL250V (20 x 5 mm, 6.3 A slow-blow); F8 and F7 monitor sound, F1AL250V (1.0 A fast-blow); F5 RMC FLT alarm,…
View on the Ziton ZP3 pageZiton ZP3
Internal supply LEDs 37, 15, 14, 8, 7, 2 and 4
The legend lists these green LEDs as supply indicators: on means the supply is on and off means the supply is faulty. LED 37: internal 24 V DC supply. LED 15: internal supply for the CPU (5 V DC). LED 14: internal…
View on the Ziton ZP3 pageZiton ZP3
LED 1: battery charging
LED 1 is listed in the legend as the battery charging indicator.
View on the Ziton ZP3 pageZiton ZP3
Power supply LED 18: earth fault
Diagnostic LED 18 on the ZP3 power supply/main board: the legend lists it as default off, and green on means an earth fault.
View on the Ziton ZP3 pageZiton ZP3
Power supply LED 19: loop fault
Diagnostic LED 19: the legend lists it as default off, and green on means a loop fault.
View on the Ziton ZP3 pageZiton ZP3
Power supply LED 20: sounder fault
Diagnostic LED 20: the legend lists it as default off, and green on means a sounder fault.
View on the Ziton ZP3 pageZiton ZP3
Power supply LED 21: ADC failure
Diagnostic LED 21: the legend lists it as default off, and green on means an ADC (analogue-to-digital converter) failure.
View on the Ziton ZP3 pageZiton ZP2-AF1
Low battery
The ZP2-AF1 is running on battery power and the remaining charge may be insufficient for continued operation.
View on the Ziton ZP2-AF1 pageZiton ZP2-AF2-99
Low battery
The ZP2-AF2-99 is running on battery power and the remaining charge may be insufficient for continued operation.