Panel fault records

Fault records by panel

Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.

Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.

Want to test yourself? Try the free daily fault challenge.

25 matches for “earth fault”

Notifier by Honeywell ID3000

Earth Fault

Source-checked

The earth fault monitor detects the presence of an earth on the positive or negative sides of the system. Should this condition occur, disconnect the field circuit wiring one cable at a time and view the LED at the top…

View on the Notifier by Honeywell ID3000 page

Ziton ZP2-FR

Earth fault

Source-checked

The yellow Earth Fault LED indicates an earth isolation fault. Earth fault reporting can be switched off under Panel setup > Other settings > Fault notification ("Earth", available on fire alarm control panels and…

View on the Ziton ZP2-FR page

Morley-IAS ZXSe

Earth Fault

Source-checked

Yellow Earth Fault indicator on the ZX series panel: an earth connection fault has occurred on a cable. To clear it, correct the fault condition and then perform a panel reset (page 7). The alphanumeric display shows a…

View on the Morley-IAS ZXSe page

Fike Twinflex

EARTH FAULT LED

Source-checked

Yellow EARTH FAULT indicator, flashing: the manual says an earth fault has been detected where a path exists from the circuit wiring to earth. Remove circuits one at a time to discover which one, and then rectify.

View on the Fike Twinflex page

Nittan Evolution

Earth Negative Fault

Source-checked

Something is shorting to earth on the negative side. Located using the same method as an Earth Positive Fault, but looking for shorts to loop negative rather than positive.

View on the Nittan Evolution page

Nittan Evolution

Earth Positive Fault

Source-checked

Something is shorting to earth on the positive side (usually through a cable screen). Most earth faults occur on the addressable loop — disconnect all loop connections and reset the panel; if no earth fault is reported…

View on the Nittan Evolution page

C-TEC ZFP

Earth fault

Source-checked

The ZFP earth-fault monitoring circuitry has detected an abnormal system connection to earth.

View on the C-TEC ZFP page

C-TEC XFP

Earth fault

Source-checked

The XFP earth-fault monitoring has detected an abnormal connection between the fire system and earth.

View on the C-TEC XFP page

Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e)

Earth Fault

Source-checked

Front-panel indicator on the DX Dimension Series panel (yellow). Function per the manual: an earth connection fault has occurred on a cable. How to clear, per the manual: correct the fault condition and then perform a…

View on the Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e) page

Fike Safety Technology CIE-A-200

Earth Fault

Source-checked

Per the manual, if the panel detects a short circuit or leakage current to earth/screen from one of its supply rails (0 V or +Ve) an Earth Fault is displayed. The normal voltage between 0 V and Earth SCRN is 1.7 V; the…

View on the Fike Safety Technology CIE-A-200 page

Fike Safety Technology Quadnet

Earth Fault

Source-checked

Per the manual, if the panel detects a short circuit to earth/screen from one of its supply rails (0 V or +ve) an Earth Fault is displayed. Remove the circuit cables one at a time and reset the system: when the faulty…

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

EARTH FAULT LED

Source-checked

Yellow EARTH FAULT indicator, flashing: the manual says an earth fault has been detected where a path exists from the circuit wiring to earth; remove circuits one at a time to discover which one, and then rectify. An…

View on the Fike Safety Technology Quadnet page

Notifier by Honeywell ID50 / ID60

EARTH FAULT

Source-checked

Message shown on the ID50/ID60 panel. The manual's Appendix 3 gives the meaning as: A wiring fault has been detected to earth. Action listed in the manual: The fault can be narrowed down by systematically disconnecting…

View on the Notifier by Honeywell ID50 / ID60 page

Zeta Premier Elite (4 to 8 zone)

Earth fault

Source-checked

Per the manual, an earth fault indicates that something is shorting to earth, usually through the cable screen. Disconnect the earth screens one at a time to determine the problem line. Connecting other equipment, for…

View on the Zeta Premier Elite (4 to 8 zone) page

Ziton ZP3

Power supply LED 18: earth fault

Source-checked

Diagnostic LED 18 on the ZP3 power supply/main board: the legend lists it as default off, and green on means an earth fault.

View on the Ziton ZP3 page

Advanced MxPro 5

Earth fault

Source-checked

The panel's internal earth-monitoring circuit (Earth Volts) reads outside its normal band. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists Too…

View on the Advanced MxPro 5 page

Kentec Syncro AS

Earth fault

Source-checked

The panel has detected leakage to earth; the manual specifies indication below 30 kOhm from +28 V or 0 V to earth.

View on the Kentec Syncro AS page

Fike Safety Technology CIE-A-400

Earth Fault

Source-checked

The CIE-A-400 has detected a short or leakage path between earth or screen and either 0 V or a positive circuit conductor.

View on the Fike Safety Technology CIE-A-400 page

Global Fire Equipment Orion (2/4/8 Zone)

EARTH FAULT

Source-checked

When this indicator is on, there is leakage current flowing between the earth connection/wiring and any other wire connected to the panel.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Eaton Fire xDetect

Earth Fault

Source-checked

The xDetect panel has detected an unintended connection from a panel input or output to earth.

View on the Eaton Fire xDetect page

Eaton Fire xDetect Mini

Earth Fault

Source-checked

The xDetect Mini panel has detected an unintended connection from a panel input or output to earth.

View on the Eaton Fire xDetect Mini page

Zeta Simpo

Earth Fault

Source-checked

Resistive connection between some signals and earth, below 10kΩ.

View on the Zeta Simpo page

Zeta Premier

EARTH

Source-checked

Power supply status indicator on the Zeta Premier AL power supply board. The manual lists it as: Earth fault, printed in the manual as “Earth fault (disabled)”; the diagram beside it shows the earth fault monitoring…

View on the Zeta Premier page

C-TEC XFP

PSU fault

Source-checked

The XFP power-supply monitoring indicates a supply, battery or earth-monitoring problem.

View on the C-TEC XFP page

Notifier by Honeywell ID3000

Signal Degraded

Source-checked

Data returned from a loop device is being corrupted over a period of time. Action - Check: a. The continuity of loop screens; b. The screen is connected to earth at one point only (normally at the panel). Note: the…

View on the Notifier by Honeywell ID3000 page